Mike Krzyzewski is really a famous coach of Dream Team. She has coached north america men's basketball team for some time, that's clinched numerous medals for his country. Following London Olympic was over, Krzyzewski told The Associated Press that this game will be his final one as national coach, a job he's held for seven years. He had left open the possibility of staying with the team beyond the London Games, when practice on Saturday said these will be his last Olympics.When asked if he was sure, Krzyzewski didn't hesitate before again saying, "yes," this will be his last game "If we could win it, then it might be three major championships in a row, i always do not know when that has been done because we haven't usually won the globe championships," Krzyzewski said. "It becomes an enormous thing for the program." Whatever, he's an awesome coach. His achievement are going to be remembered by the country.

秋葵视频下载,

CR-JP戶外綜合配電櫃

更新:2013/9/27 15:22:53      点击:
  • 産品品牌   
  • 産品型號   CR-JP
  • 産品描述

    CR-JP戶外綜合配電櫃,是上海人民电气有限公司 http://www.shamandq.com 为您提供的关于CR-JP戶外綜合配電櫃型号,CR-JP戶外綜合配電櫃价格,有关CR-JP戶外綜合配電櫃...

産品介紹

JP系列戶外綜合配電箱,是根據電網建設改造要求及電網運行經驗,本著安全、經濟、合理、可靠的原則而設計的,具有電能分配、控制、保護、無功補償、電能計量等多功能的新型戶外綜合配電箱,同時可根據用戶要求加入漏電保護功能。産品具有結構新穎、合理、防護等級高、安裝調試、維護及檢修方便等優點。産品符合GB7251.1-1997,並通過了3C認證,是目前電網改造中理想的低壓成套裝置。

JP系列戶外綜合配電箱適用于0.4kV電壓等級的電能分配、計量、保護和無功功率自動補償。

二、産品特點

JP系列戶外綜合配電箱,可具有配電,補償,計量三種基本功能。用戶可根據需要選擇不同方案,具體方案號如下:

01——配电+补偿+计量     02——配电+补偿     03——配电+计量     04——补偿+计量         05——配电                   06——计量             07——补偿

三、主要性能

1、響應及時迅速,補償效果好,工作可靠,也可根據用戶需求加入漏電保護器。

2、保護功能:過壓、過載、欠壓、欠流、短路、缺相、零序超限等功能

3、自動運行功能:停電推出、送電後延時10s自動恢複

4、可提高電網功率因數達到0.95以上

運行條件

1、环境温度:   -40℃~+55℃

2、空氣相對濕度:≤90%(相對環境溫度爲20℃~25℃)

3、海拔高度:  不超過2000m

4、环境条件:   适用于箱体内安装,不适用于有火灾、爆炸危险、严重污秽、化学腐蚀及剧烈震动的地方。

5安裝位置:與地面垂直的傾斜度不超過5o

五、技術參數:

1、額定電壓:400V

2、額定頻率:50Hz

3、配用变压器容量分别为: 30、50、63、80、100、125、 160、200、 250、 315(kVA )

4、電容分組:一般分2、3、4、5級,如用戶有特殊要求,按用戶要求配置。

5饋電回路一般分3路,每路按所配變壓器總容量的40%~60%配置,如用戶有特殊要求,按用戶要求。

6、補償方式:循環投切,編碼投切,模糊控制自動投切。

7、控制物理量:無功功率或無功電流

8、最快響應時間:≤20ms

六、安裝調試

1、安裝前檢查

  檢查設備是否完好無損,隨機資料及配件是否齊全,如發現問題應及時與廠家聯系。

2、安裝接線

1)産品安裝與變壓器台架下方,配電箱固定件由用戶自備。

2)産品的安裝參照安裝示意圖(見圖2),進出線采用電纜或穿管絕緣導線與變壓器或低壓饋電架空線連接。

3、通電前的檢查與實驗

  産品安裝完畢後,投入運行前需進行如下項目的檢查與實驗。

1)檢查箱體內是否幹燥、清潔。

2)電器元件的操作機構是否靈活,不應有卡澀或操作力過大現象。

3)主要電器元件的通斷是否可靠、准確,輔助接點的通斷是否可靠准確。

4)儀表指示與互感器的變比及極性是否正確。

5)母線連接是否良好,其絕緣支撐件、安裝件及附件是否牢固可靠。

6)用500伏兆歐表測量絕緣電阻不得低于10兆歐,浏覽量時應斷開電子設備、電容器及消耗電流的器件如線圈。

4、通電調試

1)電能表調試

饋電主回路通以額定電壓和一路負載,電能表應能運轉正常。

饋電主回路施加額定電壓,斷開全部負載電能表轉動不應超過1圈。

2)無功功率自動補償控制器的調試

  控制器出廠裏投入、切除門限,延時時間,過壓門限,已按有關標准整定,如需重新整定,請按照無功功率自動補償控制器的使用說明進行調整。

七、使用與維護注意事項

1)必須由合格的電氣人員進行該産品的操作、維護和檢修。

2)維修時要先斷開電源,待補償電容器放電完畢後再進行維修。

3)電纜進出處應采用可靠密封措施,確保運行安全。

4)斷路器应定期进行维修。

5)如綜合配電箱主開關選用刀開關,則必須在無負荷情況下,分合刀開關,以確保人身安全。

6)如用戶選用帶有無功補償裝置的綜合配電箱,則産品中的無功功率自動補償控制器,應嚴格按照使用說明書操作、檢驗。

更多産品